TilliT Edge
TilliT Edge software
TilliT uses a specialised Internet of Things (IoT) device called TilliT Edge to establish a digital connection between your equipment and operators. TilliT Edge is highly versatile, allowing for seamless integration with various devices, including SCADA systems, PLCs, or wireless counters, making it effortless to install in any production environment without complexity.
TilliT Edge is shipped ready to be integrated into your facility, without the need for coding or engineering. It supports a wide range of protocols, including OPC-UA, Ethernet/IP, Profinet, and Modbus.
TilliT Edge Device
TilliT Edge can be installed two different ways.
We suggest to involve the relevant personnel within your company to make the appropriate choice for your existing systems
Edge Device
You will receive a physical device with the preloaded TilliT Edge software. This device is specifically selected to be placed on the production floor, inside a control cabinet, and uses two network interfaces to separate your business and automation network. Choose this option if you require direct connection to PLC's. This setup will require an electrician to install the device.
Description | Requirement |
---|---|
Internet Connectivity | Yes (Static or DHCP) |
Automation Network Connectivity | Yes (Static or DHCP) |
Up/Down Bandwidth Min | 5mpbs |
Up/Down Usage Min | 10GB/Month |
Ethernet Connectivity | CAT-6E cable (If automation network is isolated from internet, then a cable to each network is required) |
Wi-Fi Connection | Optional (requires high signal strength with no drop outs) |
4G Connection | Optional (contact if relevant to your installation) |
Protocol Support | OPC-UA, MODBUS TCP, Ethernet/IP, Profinet |
Power | 24V |
Mounting | DIN Rail mount |
Dimensions | On request (supply constraints mean the device sent may be different) |
NTP Service | *.debian.pool.ntp.org (can be changed upon request to connect to a local NTP service) |
DNS | 8.8.8.8 (can be changed upon request to connect to a local DNS) |
If connecting via a Static IP, you need to supply the following information to TilliT to correctly configure the TilliT Edge device for you. Consider the same for a wireless gateway if using.
IP Address (e.g. 192.168.0.5)
Default Gateway (e.g. 192.168.0.1)
Subnet (e.g. 255.255.255.0)
If your network is behind a firewall, you will need to allow the device to reach the following endpoints.
Domain Name | Protocol | Ports |
---|---|---|
*.amazonaws.com | TCP | 8883,8443,443 |
raspbian.raspberrypi.org | TCP | 80 |
deb.nodesource.com | TCP | 443 |
*.debian.pool.ntp.org | UDP | 123 |
A comment on *.amazonaws.com. Since AWS utilises microservice and dynamic CDN architecture we connect to multiple amazon endpoints that may change. We also may increase the number of services we utilise. For this reason, we recommend using the *.amazonaws.com
TilliT Edge Device level firewall
All TilliT Edge devices come with an inbuilt firewall service called iptables. It restricts what connections the device is allowed to make. You can see the exact rules that we have setup below. To summarize, the device will never allow an external device to initate a connection, all connections are initiated by the TilliT Edge device.
Self-Managed Installation
If a physical device is not required, and you are connecting to data sources that are accessible on a network, you can run a Docker instance on a local machine capable of running Linux that you provide. This installation is highly recommended if you have an existing managed IT infrastructure where all data sources are accessible on the network.
Description | Requirement |
---|---|
Internet Connectivity | Yes |
Automation Network Connectivity | Yes |
Up/Down Bandwidth Min | 5mpbs |
Up/Down Usage Min | 10GB/Month |
Protocol Support | OPC-UA, MODBUS TCP, Ethernet/IP, Profinet |
Operating System | Ubuntu 22.02 (contact if other is required) |
CPU | 2xCores@2.8Ghz |
RAM | 4GB |
HDD | 20GB (installation size) |
Docker Engine | Version 20.10 |
Docker Compose | Version 2.15.1 |
If your network is behind a firewall, you will need to allow the device to reach the following endpoints.
Domain Name | Protocol | Ports |
---|---|---|
*.amazonaws.com | TCP | 8883, 8443, 443 |
archive.ubuntu.com | TCP | 80 |
deb.nodesource.com | TCP | 443 |
ntp.ubuntu.com | UDP | 123 |
*.docker.io | TCP | 443 |
*.docker.com | TCP | 443 |
With even just a counter, TilliT is able to provide availability and performance metrics to a reporting system via a web portal or via API connection
Last updated